Basics about this S7200 SMART PLC
1) For programming of this PLC you need Microwin SMART software. Its similar like Microwin. If you have project backup of S7 200 PLC then same you can open in Microwin SMART by changing only extension as .SMART and download in S7200 SMART PLC.
2) S7200 SMART PLC having CPU range starting from ST/SR20,ST/SR30,ST/SR40 and ST/SR60
Its depend upon the IO handaling capacity and memory of PLC. (Sr means relay output and ST means Standard output)
Features
1) Onboard Ethernet (RJ45) Port for communication with PC. No need any more MPI/PPI cable for downloading or uploading program
2) With Same ethernet port you can communicate with HMI,SCADA(PC Access OPC),PLC's( LOGO!/S7200 SMART/S71200/S7300/S7400/S71500) via GET PUT ( No Profinet/TCP communication)
3) High speed counter and pulse output
4) SMS functionality via Modem
5) On board RS485 board for Serial, USS , Free port communication,Modbus RTU
6) Signal board of RS232/RS485
7) Motion Functionality :- Cost effective solution for Motion-Micro Automation application with V20/V90 drive.
7) PID control via Wizard
8) Communication Capability
a) S7 connection with SIMATIC PLC via GET/PUT
b) OPC communication via PC access OPC server
c) Modbus RTU communication via RS485
d) Ethernet communication with SIMATIC HMI
e) USS / Free port protocol communication. (Bard-code scanner/Serial Printer/weighing scale etc)
f) Profibus Slave card : communication with Any SIMATIC /Non SIMATIC Profibus Master
9) It has 8MB memory for data logging
10) Any Micro SD memory card can be used for Firmware update /Program upload/Download/Reset factory default
Product Details:
Brand | Siemens |
Memory Size | 30 kbyte; Program memory |
Weight | 528.2g |
Interfaces | 1 |
Width | 175mm |
Height | 100mm |
Inrush Current Max | 11.5 A; at 28.8 V |
Power Loss | 20W |
Number of Digital Outputs | 24 |
Number of Digital Inputs | 36 |
Relative Humidity | 95 % |
Cable Length | 500 m; 50m shielded for HSC inputs |
Depth | 81mm |
Model No | CPU ST60 |
Supply Voltage | 24 V DC |
Current Output Max | 300 mA; 24 V DC Sensor Power |
Backup Time | 7 d |
Current Consumption Max | 710 mA; 24 V DC |
Interface Type | Ethernet |
CPU Processing Times | 150 ns; / instruction,1.2 us; / instruction,3.6 us; / instruction |
Rail Mounting | Yes; Standard - DIN rail |
Product Details:
Brand | Siemens |
Memory Size | 24 kbyte; Program memory |
Weight | 410.3g |
Interfaces | 1 |
Current Output Max | 300 mA; 24 V DC Sensor Power |
Power Loss | 18W |
Depth | 81mm |
Cable Length | 500 m; 50m shielded for HSC inputs |
Model No | Rail mounting |
Inrush Current Max | 11.7 A; at 28.8 V |
Interface Type | Ethernet |
Width | 125mm |
Number of Digital Inputs | 24 |
Number of Digital Outputs | 16 |
Supply Voltage | 24 V DC |
Height | 100mm |
CPU Processing Times | 150 ns; / instruction,1.2 us; / instruction,3.6 us; / instruction |
Relative Humidity | 95 % |
Input Current | 680 mA; 24 V DC |
Product Details:
Brand | Siemens |
Supply Voltage | 24 V DC |
Weight | 320g |
Input Current | 720 mA; 24 V DC |
Relative Humidity | 95% |
Depth | 81mm |
CPU Processing Times | 150 ns; / instruction,1.2 us; / instruction,3.6 us; / instruction |
Digital Inputs | 12 |
Interfaces | 1 |
Height | 100mm |
Width | 90mm |
Inrush Current Max | 11.7 A; at 28.8 V |
Output Current | 300 mA; 24 V DC Sensor Power |
Micro Memory Card | Yes; microSDHC Card (optional) |
Degree Protection | IP20 |
Model No | CPU ST20 |
Power Loss | 20W |
Memory Size | 12 kbyte; Program memory |
Time of Day | 7day |
Cable Length | 500 m; 50m shielded for HSC inputs |
Product Details:
Brand | Siemens |
Power Loss | 12 W |
Supply Voltage | 24 V DC |
Memory Size | 18 kbyte; Program memory |
Micro Memory Card | Yes; microSDHC Card (optional) |
CPU Processing Times | 150 ns; / instruction,1.2 us; / instruction,3.6 us; / instruction |
Interfaces | 1 |
Weight | 375g |
Model No | CPU ST30 |
Output Current | 300 mA; 24 V DC Sensor Power |
Rail Mounting | Yes; Standard - DIN rail |
Number of Digital Inputs | 18 |
Relative Humidity | 95 % |
Width | 110 mm |
Inrush Current Max | 6 A; at 28.8 V |
Backup Time | 7 d |
Cable Length | 500 m; 50m shielded for HSC inputs |
Number of Digital Outputs | 12 |
Input Current | 624 mA; 24 V DC |
Depth | 81mm |
Height | 100mm |